Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/20/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 03/29/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VENT ON CONDENSATE DRAIN MUST BE DOWNSTREAM OF THE TRAP 2) DO NOT TERMINATE CONDENSATE INTO A SEWER VENT 3) PAINT EXPOSED PVC WITH LATEX PAINT 4) BLOCK AND CLAMP EVERY 4' 5) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE 6) SUPPORT GAS LINE 7) PROVIDE A SEDIMENT TRAP 8) PROVIDE MINIMUM R8 DUCT LINES IN EXPOSED DUCT ON THE ROOF 9) PROVIDE A BUSHING ELECTRIC DISCONNECT 10) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF 11) PROVIDE GREEN WIRE FOR GROUND 12) ELECTRIC DISCONNECT OVERFUSED-35 AMP IS MAXIMUM |