Permit: T10ME00165

Parcel: 134110900


Addresses:

8045 E BEVERLY ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/20/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
03/29/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) VENT ON CONDENSATE DRAIN MUST BE DOWNSTREAM OF THE TRAP
2) DO NOT TERMINATE CONDENSATE INTO A SEWER VENT
3) PAINT EXPOSED PVC WITH LATEX PAINT
4) BLOCK AND CLAMP EVERY 4'
5) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
6) SUPPORT GAS LINE
7) PROVIDE A SEDIMENT TRAP
8) PROVIDE MINIMUM R8 DUCT LINES IN EXPOSED DUCT ON THE ROOF
9) PROVIDE A BUSHING ELECTRIC DISCONNECT
10) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF
11) PROVIDE GREEN WIRE FOR GROUND
12) ELECTRIC DISCONNECT OVERFUSED-35 AMP IS MAXIMUM