Permit: T10ME00159

Parcel: 12215250A

Inspection Status: Not ready for Inspection

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/03/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
04/26/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER CONTRACTOR
04/22/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE PLANS, PERMIT AND PRESSURE TEST ON ALL NEW GAS PIPING
2) PROVIDE THE LISTING FOR THE COATING USED ON EXPOSED ARMAFLEX-COAT ALL OF THE ARMAFLEX NOT JUST THE FRONT SIDE
3) PROVIDE TEST ON DUCT SMOKE DETECTOR
04/13/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE 1" CLEARANCE TO COMBUSTIBLES AT B-VENT
2) PLANS AND PERMITS ARE TO BE ON SITE AT ALL TIMES
3) LEVEL UNITS SO EASY TRAPS WILL FUNCTION CORRECTLY
4) DUCT SMOKE DETECTORS SUPERVISORY TO BE LOCATED IN A CONTINOUSLY MONITORED LOCATION
5) PROVIDE APPROVED PLANS AND PERMIT ON NEW GAS PIPING
6) PROVIDE APPROVED GROUND AT COND. DISCONNECTS
7) REFER TO PLANS AND MANUFACTURES INSTALLATION INSTRUCTIONS ON EXTERIOR PIPE INSTULATION COVERINGS
8) PROVIDE DUCT SMOKE DETCTOR TEST X2