Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/03/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/26/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER CONTRACTOR |
|
| 04/22/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE PLANS, PERMIT AND PRESSURE TEST ON ALL NEW GAS PIPING 2) PROVIDE THE LISTING FOR THE COATING USED ON EXPOSED ARMAFLEX-COAT ALL OF THE ARMAFLEX NOT JUST THE FRONT SIDE 3) PROVIDE TEST ON DUCT SMOKE DETECTOR |
|
| 04/13/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE 1" CLEARANCE TO COMBUSTIBLES AT B-VENT 2) PLANS AND PERMITS ARE TO BE ON SITE AT ALL TIMES 3) LEVEL UNITS SO EASY TRAPS WILL FUNCTION CORRECTLY 4) DUCT SMOKE DETECTORS SUPERVISORY TO BE LOCATED IN A CONTINOUSLY MONITORED LOCATION 5) PROVIDE APPROVED PLANS AND PERMIT ON NEW GAS PIPING 6) PROVIDE APPROVED GROUND AT COND. DISCONNECTS 7) REFER TO PLANS AND MANUFACTURES INSTALLATION INSTRUCTIONS ON EXTERIOR PIPE INSTULATION COVERINGS 8) PROVIDE DUCT SMOKE DETCTOR TEST X2 |