Permit: T10ME00118

Parcel: 128140900


Addresses:

5255 E 20TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/23/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
03/17/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
03/16/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) 3/8" I.D. X 36" GAS FLEX NOT ADEQUATE FOR 90,000 BTU
2) PROVIDE THE REQUIRED GFI SERVICE RECEPT FOR THE CONDENSOR WITH A BUBBLE TYPE COVER
3) EXTEND FURNACE VENT MINIMUM 3' ABOVE COMBUSTION AIR INTAKE
03/10/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE ACCESS TO UNIT
03/09/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*