Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 03/17/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/16/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) 3/8" I.D. X 36" GAS FLEX NOT ADEQUATE FOR 90,000 BTU 2) PROVIDE THE REQUIRED GFI SERVICE RECEPT FOR THE CONDENSOR WITH A BUBBLE TYPE COVER 3) EXTEND FURNACE VENT MINIMUM 3' ABOVE COMBUSTION AIR INTAKE |
|
| 03/10/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE ACCESS TO UNIT |
|
| 03/09/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |