Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T10ME00109
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/12/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
03/25/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE CANNOT BE REDUCED FROM THE OUTLET SIZE ON THE UNIT 2) PROVIDE A 1" DRAIN LINE 3) 3/8" I.D. X 12" GAS FLEX NOT ADEQUATE FOR 150,000 BTU 4) EXTEND 1 SEWER VENT MIN 2' ABOVE FRESH AIR INTAKE 5) TERMINATE CONDENSATE INSIDE THE BLDG TO AN APPROVED LOCATION 6) CANNOT TERMINATE ONTO THE PARKING LOT |