Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 03/03/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE PERMIT TO REPLACE W/H 2) THIS IS A NEW INSTALLATION NOT A CHANGE OUT PROVIDE R-8 ON ALL DUCT EXPOSED TO EXTERIOR 3) COMPLETE CONDENSATE, TERMINATE WITHIN 6" OF GRADE 4) PROVIDE APPROVED ROOF LOAD CALC. FROM CITY OF TUCSON 5) PROVIDE SERVICE RECEPTACLE ON ROOF WITHIN 25' OF EQUIPMENT |