Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/02/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) YOU CANNOT ADD 1/2" DUCT LINER TO 1 1/2" DUCT LINER TO MAKE 2" 2) PROVIDE 2" DUCT LINER INSTALLED PER CODE 3) PROVIDE THE PERMIT FOR THE SERVICE UPGRADE |
|
| 07/19/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : 1. DO NOT USE WHITE CONDUCTORS TO POWER THE A/C 2. 3/8" I.C. X24" GAS FLEX NOT ADEQUATE FOR 96,000 BTU 3. PROVIDE MINIMUM 2" R8 DUCT LINER IN EXPOSED DUCT ON THE ROOF. 4. PROVIDE A PERMIT FOR THE WATER HEATER & ELECTRICAL PANEL UPGRADE |