Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 02/23/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 1/2" GAS PIPE NOT ADEQUATE FOR 100,000 BTU FURNACE 2) DO NOT USE THE A/C CIRCUIT TO POWER THE EVAP COOLER 3) SUPPORT ELECTRIC CONDUITS 4) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT 5) SUPPORT GAS LINE 6) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF 7) NEW EXPOSED DUCT ON ROOF REQUIRES R8 INSULATION 8) A TRANSITION TO EXISTING DUCT CAN HABE 1" R4.2 |