Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/02/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
02/23/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 1/2" GAS PIPE NOT ADEQUATE FOR 100,000 BTU FURNACE
2) DO NOT USE THE A/C CIRCUIT TO POWER THE EVAP COOLER
3) SUPPORT ELECTRIC CONDUITS
4) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT
5) SUPPORT GAS LINE
6) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF
7) NEW EXPOSED DUCT ON ROOF REQUIRES R8 INSULATION
8) A TRANSITION TO EXISTING DUCT CAN HABE 1" R4.2