Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T10ME00065
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/23/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 02/08/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT THE GAS LINE 2) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE 3) PAINT ALL EXPOSED PVC WITH LATEX PAINT AND BLOCK & CLAMP EVERY 4' 4) PROVIDE AN APPROVED COVER FOR ELECTRIC J-BOX ON ROOF 5) EXTEND METAL COVER DOWN TO COVER SIDES OF CANVAS CONNECTOR 6) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF 7) NEED TO SEE CIRCUIT BREAKER |