Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 02/08/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE AN APPROVED TRAP ON CONDENSATE DRAIN LINE 2) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE 3) REMOVE DUCT TAPE USED OUTDOORS ON LINE SET 4) USE OUTDOOR TAPE OR UV ZIP TIES 5) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX 6) TERMINATE 3/8" CONDENSATE LINE INTO PVC WITH A FITTING 7) PROVIDE 1/8" PER FT. SLOPE ON PVC 8) PROVIDE A ROOF JACK 9) NEED TO SEE R8 DUCT LINER IN EXPOSED DUCT ON ROOF 10) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF |