Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/16/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 02/08/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/04/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TERMINATE CONDENSATE TO WITHIN 6" OF THE GROUND 2) PAINT EXPOSED PVC WITH LATEX PAINT AND PROVIDE MINIMUM 1/8" PER FT SLOPE ON DRAIN LINE 3) PROVIDE MINIMUM R8 DUCT LINER IN EXPOSED DUCT ON ROOF 4) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON THE ROOF IN A WATER PROOF BOX 5) 1/2" GAS PIPE NOT ADEQUATE FOR 115,000 BTU FURNACE 60' FROM METER AND PROVIDE 3/4" PIPE FROM THE METER TO THE FURNACE |