Permit: T10ME00056

Parcel: 13310216A


Addresses:

8640 E PIMA ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/29/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
03/09/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FURNACE VENT CONNECTOR HAS UPSIDE DOWN FITTINGS AND NOT SCREWED PROPERLY
2) DO NOT USE TAPE
3) CONDENSATE CANNOT TERMINATE INTO A T & P DRAIN
4) REMOVE THE VENT FROM CONDENSATE TRAP
5) PROVIDE AN OVERFLOW SENSOR
6) PROVIDE A SEDIMENT TRAP IN GAS LINE AT FURNACE
02/08/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FURNACE VENT CONNECTOR NOT SIZED CORRECTLY-USE 4"
2) PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN
3) PROVIDE A TRAP ON PRIMARY CONDENSATE DRAIN
4) CONNECT OVERFLOW SENSOR FROM PUMP
5) PROVIDE A 3/8" DRAIN LINE ON PUMP
6) REMOVE ALL UN-NECESSARY BENDS FROM GAS FLEX CONNECTOR
7) PROVIDE A SEDIMENT TRAP AT GAS CONNECTION TO FURNACE
8) SUPPORT ALL ELECTRIC CONDUIT ON ROOF
9) PROVIDE AN APPROVED BASE UNDER CONDENSORS
10) INSULATE SUCTION LINES ON ROOF
11) SUPPORT CONDENSATE DRAIN ON ROOF EVERY 6' AND TERMINATE WITHIN 6" OF THE GROUND