Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 03/09/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FURNACE VENT CONNECTOR HAS UPSIDE DOWN FITTINGS AND NOT SCREWED PROPERLY 2) DO NOT USE TAPE 3) CONDENSATE CANNOT TERMINATE INTO A T & P DRAIN 4) REMOVE THE VENT FROM CONDENSATE TRAP 5) PROVIDE AN OVERFLOW SENSOR 6) PROVIDE A SEDIMENT TRAP IN GAS LINE AT FURNACE |
|
| 02/08/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FURNACE VENT CONNECTOR NOT SIZED CORRECTLY-USE 4" 2) PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN 3) PROVIDE A TRAP ON PRIMARY CONDENSATE DRAIN 4) CONNECT OVERFLOW SENSOR FROM PUMP 5) PROVIDE A 3/8" DRAIN LINE ON PUMP 6) REMOVE ALL UN-NECESSARY BENDS FROM GAS FLEX CONNECTOR 7) PROVIDE A SEDIMENT TRAP AT GAS CONNECTION TO FURNACE 8) SUPPORT ALL ELECTRIC CONDUIT ON ROOF 9) PROVIDE AN APPROVED BASE UNDER CONDENSORS 10) INSULATE SUCTION LINES ON ROOF 11) SUPPORT CONDENSATE DRAIN ON ROOF EVERY 6' AND TERMINATE WITHIN 6" OF THE GROUND |