Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/03/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/01/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE SCHEDULE WHEN SOMEONE WILL BE HOME |
|
| 05/26/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSTATE TRAP IS INSTALLED BACKWARDS 2) DO NOT USE INSULATION TO REDUCE CLEARANCE FROM PLASTIC DRAIN PIPE. USE COPPER IF NECESSARY 3) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX AT CONDENSOR. SEE MANUFACTURE FOR PROPER COATING 4) TERMINATE CONDENSATES TO WITHIN 6" OF THE GROUND |
|
| 05/11/2010 | MECHANICAL - FINAL | Cancelled | CANCELLED PER HOMEOWNER MICHELLE CARTER #749-1971 | |
| 05/11/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
| 03/02/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A TRAP ON CONDENSATE DRAIN 2) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE 3) PVC MUST BE MINIMUM 6" FROM SINGLE WALL VENT CONNECTOR 4) PROVIDE A SECONDARY OVERFLOW SENSOR 5) 1ST FITTING ON VENT CONNECTOR IS UPSIDE DOWN 6) INSULATE SHEET METAL SLEEVE ON TOP OF FURNACE 7) PROVIDE A PROTECTION COATING ON EXPOSED ARMAFLEX AT CONDENSOR 8) PROVIDE THE RQUIRED GFI SERVICE RECEPT AT CONDENSOR 9) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT |
|
| 02/19/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CALLED NUMBER ON MESSAGE VOICE MAIL LEFT NAME AND NUMBER AFTER 15 MINUTES, NO RETURN CALL AND NO ONE HOME |