Permit: T10ME00053

Parcel: 133290580


Addresses:

8441 E SHILOH ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/03/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/01/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLEASE SCHEDULE WHEN SOMEONE WILL BE HOME
05/26/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDENSTATE TRAP IS INSTALLED BACKWARDS
2) DO NOT USE INSULATION TO REDUCE CLEARANCE FROM PLASTIC DRAIN PIPE. USE COPPER IF NECESSARY
3) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX AT CONDENSOR. SEE MANUFACTURE FOR PROPER COATING
4) TERMINATE CONDENSATES TO WITHIN 6" OF THE GROUND
05/11/2010 MECHANICAL - FINAL Cancelled CANCELLED PER HOMEOWNER MICHELLE CARTER #749-1971
05/11/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
03/02/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A TRAP ON CONDENSATE DRAIN
2) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
3) PVC MUST BE MINIMUM 6" FROM SINGLE WALL VENT CONNECTOR
4) PROVIDE A SECONDARY OVERFLOW SENSOR
5) 1ST FITTING ON VENT CONNECTOR IS UPSIDE DOWN
6) INSULATE SHEET METAL SLEEVE ON TOP OF FURNACE
7) PROVIDE A PROTECTION COATING ON EXPOSED ARMAFLEX AT CONDENSOR
8) PROVIDE THE RQUIRED GFI SERVICE RECEPT AT CONDENSOR
9) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT
02/19/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CALLED NUMBER ON MESSAGE VOICE MAIL LEFT NAME AND NUMBER AFTER 15 MINUTES, NO RETURN CALL AND NO ONE HOME