Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T10ME00032

Parcel: 136173810


Addresses:

8327 E SALINAS DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/01/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
02/26/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) TERMINATE CONDENSATE PUMP DRAIN LINE INTO PVC WITH A FITTING
2) PAINT EXPOSED PVC WITH LATEX PAINT
3) SEAL HOLE IN COMBUSTION AIR SCREEN ON ROOF