Permit: T10ME00030

Parcel: 118042700

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Permit Number - T10ME00030

Inspection Description - MECHANICAL - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
01/29/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) B-VENT IS UPSIDE DOWN
2) B-VENT CANNOT BE CUT
3) PROVIDE ACCESS TO SECOND F.A.U.
4) ITEMS 1-6 DATED 1/19/10 HAVE BEEN CORRECTED
01/25/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ONE HOME
01/19/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE FUSES AT C.U. UNITS
2) FOAM INSULATION TO BE WEATHER COATED
3) PROVIDE SECONDARY DRAIN ON COILS
4) CONDENSATE PRIMARY DRAINING UP HILL
5) REPLACE OR REPAIR LINE SET INSULATION INDOORS
6) PROVIDE FILTERS IN ALL RETURN GRILLS
7) PROVIDE ACCESS TO SECOND F.A.U.