Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
Permit Number - T10ME00030
Inspection Description - MECHANICAL - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/29/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) B-VENT IS UPSIDE DOWN 2) B-VENT CANNOT BE CUT 3) PROVIDE ACCESS TO SECOND F.A.U. 4) ITEMS 1-6 DATED 1/19/10 HAVE BEEN CORRECTED |
|
01/25/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ONE HOME |
|
01/19/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE FUSES AT C.U. UNITS 2) FOAM INSULATION TO BE WEATHER COATED 3) PROVIDE SECONDARY DRAIN ON COILS 4) CONDENSATE PRIMARY DRAINING UP HILL 5) REPLACE OR REPAIR LINE SET INSULATION INDOORS 6) PROVIDE FILTERS IN ALL RETURN GRILLS 7) PROVIDE ACCESS TO SECOND F.A.U. |