Case: T10FR02705

Parcel: 134270010


Addresses:

7600 E BROADWAY BL


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR02705

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
12/21/2010 VIOL - MEANS OF EGRESS Violation 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate…
The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator.

_____ Repair or replace batteries in emergency lighting
12/21/2010 VIOL - MEANS OF EGRESS Violation 1011.1 Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.

__Provide exit signs for office area.

__Re- arrange exit signs all floors
12/21/2010 VIOL - MEANS OF EGRESS Violation 1011.2 - Illumination. Exit signs shall be internally or externally illuminated.

_____ Repair/replace exit signs