Case: T10FR02702

Parcel: 11901076A


Addresses:

3372 S 6TH AV


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T10FR02702

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
12/21/2010 VIOL - BUILDING SVCS & SYSTEMS Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with portable appliances.

__Remove/replace all unprotected extension cords being used as permanent wiring.
___ Bakery area, Vegetables area.
12/21/2010 VIOL - BUILDING SVCS & SYSTEMS Violation 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
___ Vegetables area.
12/21/2010 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.