Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T10FR02640
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2011 | INSP - FULL | Approved | NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. | |
| 12/14/2010 | INSP - FULL | Violation | 1.) TFC 605.4.2 POWER STRIPS ARE CONNECTED IN SERIES IN TYNAN NURSES OFFICE ON 2ND FLOOR. | |
| 12/14/2010 | INSP - FULL | Violation | 2.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN FREEZER. | |
| 12/14/2010 | INSP - FULL | Violation | 3.) TFC 901.6.2 THE SPRINKLER SYSTEM ANNUAL INSPECTION REPORT MUST BE SUBMITTED UPON RE-INSPECTION. |