Case: T10FR02631

Parcel: 117033520


Addresses:

638 E UNIVERSITY BL

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
02/03/2011 VIOL - MEANS OF EGRESS Approved
12/14/2010 VIOL - MEANS OF EGRESS Violation 1008.1.8.5 Unlatching. The unlatching of any door or
leaf shall not require more than one operation.
1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.
1028.8 Panic hardware. Where panic and fire exit hardware is installed, the panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code.

____REMOVE ONE OF THE DOORKNOBS FROM THE KITCHEN SECURITY GATE.
____REMOVE DOUBLE KEYED DEADBOLTS ON BOTH EXIT DOORS FROM 3RD FLOOR.