Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T10FR02445
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/23/2010 | VIOL - MEANS OF EGRESS | Correction Required | 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ Remove the slide bolt from the ---- egress door, as bolt lock of any kind are not permitted 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____ Fix, repair, and/or replace all exit signs in order to meet code standards |