Case: T10FR02426

Parcel: 11445262J

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR02426

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
12/13/2010 VIOL - MEANS OF EGRESS Approved All approved / closed.
11/19/2010 VIOL - MEANS OF EGRESS Violation Exit Signs- light and back up power:
1011.5.3 Power source. Exit signs shall be illuminated at
all times. To ensure continued illumination for a duration of
not less than 90 minutes in case of primary power loss, the
sign illumination means shall be connected to an emergency
power system provided from storage batteries, unit equipment
or an on-site generator. The installation of the emergency
power system shall be in accordance with Section
2702 of the International Building Code.

______ Repair all exit signs and battery back up system.