3730 N STONE AV

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
11/12/2010 VIOL - MEANS OF EGRESS Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system.

_____1. All EXIT signs shall have emergency back-up power.
LOCATIONS: northwest EXIT signs, southeast EXIT sign, southwest EXIT sign and the EXIT sign in Laura's office.
NOTE: Check all signs in low lighting to ensure illumination.
11/12/2010 VIOL - MEANS OF EGRESS Correction Required IFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists:
2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F,M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided:
2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, 2.3. The use of the key-operated locking device is revocable by the fire code official for due cause.

_____1. Post the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" on the inside or the main entrance door.