12/15/2010 | VIOL - MEANS OF EGRESS | Approved | All approved - Ligh for man door may be added later, but is approved "as is" now... Good job! Closed. |
|
11/10/2010 | VIOL - MEANS OF EGRESS | Violation | Exit Signs- light and back up power: 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. ______ Repair all exit signs and battery back up system. |
|
11/10/2010 | VIOL - MEANS OF EGRESS | Violation | Bolt lock: TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. ______Remove bolt lock. |
|
11/10/2010 | VIOL - MEANS OF EGRESS | Violation | Emergency lighting: IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights. |
|
11/10/2010 | VIOL - MEANS OF EGRESS | Violation | Other: Poorly light door: It is the recommendationof this Fire Marshal to install a lit exit sign with a back up battery and Emergency [spot] lighting in the area - on the "man door" by the loading dock door. ______ Lighting added as per request by Ma 30. |