Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T10FR02384

Parcel: 11445262G

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR02384

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
12/15/2010 VIOL - MEANS OF EGRESS Approved All approved - Ligh for man door may be added later, but is approved "as is" now...
Good job! Closed.
11/10/2010 VIOL - MEANS OF EGRESS Violation Exit Signs- light and back up power:
1011.5.3 Power source. Exit signs shall be illuminated at
all times. To ensure continued illumination for a duration of
not less than 90 minutes in case of primary power loss, the
sign illumination means shall be connected to an emergency
power system provided from storage batteries, unit equipment
or an on-site generator. The installation of the emergency
power system shall be in accordance with Section
2702 of the International Building Code.

______ Repair all exit signs and battery back up system.
11/10/2010 VIOL - MEANS OF EGRESS Violation Bolt lock:
TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.

______Remove bolt lock.
11/10/2010 VIOL - MEANS OF EGRESS Violation Emergency lighting:

IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located]

______Fix all inoperative emergency lights.
11/10/2010 VIOL - MEANS OF EGRESS Violation Other: Poorly light door:
It is the recommendationof this Fire Marshal to install a lit exit sign with a back up battery and Emergency [spot] lighting in the area - on the "man door" by the loading dock door.

______ Lighting added as per request by Ma 30.