Inspection History: VIOL - FIRE SERVICE FEATURES
Case Number - T10FR02384
Inspection Description - VIOL - FIRE SERVICE FEATURES
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/15/2010 | VIOL - FIRE SERVICE FEATURES | Approved | ||
11/10/2010 | VIOL - FIRE SERVICE FEATURES | Violation | FIRE DEPARTMENT ACCESS TO EQUIPMENT: 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. ______ Place a sign "Fire- Electrical access" on outer door, and "Fire- Electrical Room" on inner door where main breakers are. [3" Red on White decal applied permanantly to the door. |