Case: T10FR02384

Parcel: 11445262G

Inspection Status: Approved

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Case Number - T10FR02384

Inspection Description - VIOL - PRECAUTION AGAINST FIRE

Inspection Status - Approved

Date Description Inspector Results Comments
12/15/2010 VIOL - PRECAUTION AGAINST FIRE Approved
11/10/2010 VIOL - PRECAUTION AGAINST FIRE Violation Housekeeping:

TFC 304.1 Waste accumulation prohibited. Combustible waste
material creating a fire hazard shall not be allowed to accumulate
in buildings or structures or upon premises.
______ Keep area around building clear and neat. Stack pallets neatly. Keep FDC clear. [See chapter 9 - below]
11/10/2010 VIOL - PRECAUTION AGAINST FIRE Violation Clearance below sprinklers:
TFC 315.2.1 Ceiling clearance. Storage shall be maintained 24 inches (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.

______Remove storage to 18 inches or more below sprinkler head.