Case: T10FR02354

Parcel: 13313006M


Addresses:

7699 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T10FR02354

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
11/23/2010 VIOL - FIRE PROTECTION SYSTEMS Approved
11/08/2010 VIOL - FIRE PROTECTION SYSTEMS Violation Extinguishers not tagged / inspected:

TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

______ Extinguishers shall be maintained, inspected and tagged [annually] in accordance with this code.
11/08/2010 VIOL - FIRE PROTECTION SYSTEMS Violation Pull station clear and identifiable:

TFC2006/ 904.11.4 Special provisions for automatic sprinkler systems.
Automatic sprinkler systems protecting commercial- type cooking equipment shall be supplied from a
separate, readily accessible, indicating-type control valve that is identified.

______ Clear area around pull station and have it clearly marked
11/08/2010 VIOL - FIRE PROTECTION SYSTEMS Violation Class K Extinguisher:

TFC2006/ 904.11.5 Commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.

______A K class extinguisher shall be installed according to this code.
11/08/2010 VIOL - FIRE PROTECTION SYSTEMS Violation Hood system:
904.11.6 Operations and maintenance. Commercial cooking systems shall be operated and maintained in accordance with this section.

______ Hood system to be serviced, tested and tagged every 6 months. [Prep stove hood]
11/08/2010 VIOL - FIRE PROTECTION SYSTEMS Violation Extinguishers not mounted:

TFC2006/ 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm).

______ Mount extinguishers in an approved manner.