Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T10FR02353
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/13/2010 | VIOL - MEANS OF EGRESS | Approved | All approved / closed | |
11/08/2010 | VIOL - MEANS OF EGRESS | Violation | Exit Signs- light and back up power: 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. ______ Repair all exit signs and battery back up system. |
|
11/08/2010 | VIOL - MEANS OF EGRESS | Violation | Exit access, exit, and discharge path blocked: 1027.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. Security devices affecting means of egress shall be subject to approval of the fire code official. ______ Clear exit path and keep it clear [36" minimum] |
|
11/08/2010 | VIOL - MEANS OF EGRESS | Violation | Aisle widths: 1013.4.1 Groups B and M. In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches (914 mm). ***Arrange aisles to comply with this code. |
|
11/08/2010 | VIOL - MEANS OF EGRESS | Violation | Blocked exits: 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _______Clear ALL exit areas, and maintain it this way. |
|
11/08/2010 | VIOL - MEANS OF EGRESS | Violation | Emergency lighting: IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights. |