Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T10FR02347
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/23/2010 | VIOL - MEANS OF EGRESS | Approved | ||
11/05/2010 | VIOL - MEANS OF EGRESS | Violation | Blocked exit: 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _______Clear exit area, and maintain it this way. [Rm 5] |
|
11/05/2010 | VIOL - MEANS OF EGRESS | Violation | Bolt lock: TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. ______Remove bolt lock. [both Javelina Hall restrooms] |
|
11/05/2010 | VIOL - MEANS OF EGRESS | Violation | Panic Hardware: TFC2006 / 1028.8 [Tucson Fire Code Modifications] Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code. ______Remove constraint and keep clear in the future. [The "Lockdown" chain is not allowed per the fire code.] |
|
11/05/2010 | VIOL - MEANS OF EGRESS | Violation | Exit Signs- light and back up power: 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. ______ Repair all exit signs and battery back up system. |
|
11/05/2010 | VIOL - MEANS OF EGRESS | Violation | Emergency lighting: IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights. |