Case: T10FR02347

Parcel: 13313007B


Addresses:

7777 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR02347

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
11/23/2010 VIOL - MEANS OF EGRESS Approved
11/05/2010 VIOL - MEANS OF EGRESS Violation Blocked exit:
1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in
this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel.

_______Clear exit area, and maintain it this way. [Rm 5]
11/05/2010 VIOL - MEANS OF EGRESS Violation Bolt lock:
TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.

______Remove bolt lock. [both Javelina Hall restrooms]
11/05/2010 VIOL - MEANS OF EGRESS Violation Panic Hardware:

TFC2006 / 1028.8 [Tucson Fire Code Modifications] Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code.

______Remove constraint and keep clear in the future. [The "Lockdown" chain is not allowed per the fire code.]
11/05/2010 VIOL - MEANS OF EGRESS Violation Exit Signs- light and back up power:
1011.5.3 Power source. Exit signs shall be illuminated at
all times. To ensure continued illumination for a duration of
not less than 90 minutes in case of primary power loss, the
sign illumination means shall be connected to an emergency
power system provided from storage batteries, unit equipment
or an on-site generator. The installation of the emergency
power system shall be in accordance with Section
2702 of the International Building Code.

______ Repair all exit signs and battery back up system.
11/05/2010 VIOL - MEANS OF EGRESS Violation Emergency lighting:

IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located]

______Fix all inoperative emergency lights.