Case: T10FR02347

Parcel: 13313007B


Addresses:

7777 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Case Number - T10FR02347

Inspection Description - VIOL - PRECAUTION AGAINST FIRE

Inspection Status - Approved

Date Description Inspector Results Comments
11/23/2010 VIOL - PRECAUTION AGAINST FIRE Approved
11/05/2010 VIOL - PRECAUTION AGAINST FIRE Violation Clearance below ceiling:
TFC 315.2.1 Ceiling clearance. Storage shall be maintained 24 inches (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.

______Remove storage to 24 inches or more below ceiling. [room "B"]