Case: T10FR02297

Parcel: 110113660


Addresses:

4775 E GRANT RD


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T10FR02297

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
11/30/2010 VIOL - FIRE PROTECTION SYSTEMS Approved SERVICE REPORT FROM UNITED FIRE RECEIVED SHOWING DEFICIENCIES CORECTED. APPROVED.
11/02/2010 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 901.6 THE SPRINKLER SYSTEM INSPECTION DONE ON 05/14/10 NOTED THAT THE CONTROL VALVE IS NOT WORKING. 6 WHITE ESCUTCHEONS ARE MISSING, 1 ADDITIONAL SIDE WALL HEAD IS REQUIRED IN SPARE BOX AND AN NFPA MANUAL IS REQUIRED IN SPARE HEAD BOX. HAVE THESE ITEMS CORRECTED WITHIN 30 DAYS.