Case: T10FR02232

Parcel: 11206219B


Addresses:

2574 N CAMPBELL AV


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T10FR02232

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
10/27/2010 VIOL - FIRE PROTECTION SYSTEMS Correction Required 906.7 Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.

______ Service, tag, maintain, and properly hang all portable fire extinguishers according to code

912.3 Access.
Immediate access to fire department connections shall be maintained at all times and without obstruction by fences, bushes, trees, walls or any other object for a minimum
of 3 feet (914 mm).

_____Keep riser clear