Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T10FR02173

Parcel: 10607001F


Addresses:

923 W PRINCE RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR02173

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
10/20/2010 VIOL - MEANS OF EGRESS Correction Required 1008.1.8.3 Locks and latches.
Locks and latches shall be permitted to prevent operation of doors where any of the following exists…
-- 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress
side provided:
-- 2.1. The locking device is readily distinguishable as locked,
-- 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background,
-- 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause.

_____ Place the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" visibly above your main
egress door.

1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

_____ Remove the double-key lock and replace with an approved locking device such as, thumb turn lock or panic hardware





________________________________________________
(Joseph P. Longo, Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report.
(Building Representative)

____________________________
(Captain)

Re-inspection scheduled on or after ___/___/___
Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions.
Thank you.

Re-inspection passed: ___ ___ ___


___________________ Passed on: ________
(Joseph P. Longo)