Case: T10FR02105

Parcel: 13315324A

Inspection Status: Correction Required

Inspection History: INSP - AST

Case Number - T10FR02105

Inspection Description - INSP - AST

Inspection Status - Correction Required

Date Description Inspector Results Comments
10/14/2010 INSP - AST Correction Required Dear Sir or Madam,

The Tucson Fire Department has conducted a fire safety inspection at the above stated business on 10-14-2010. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code with modifications. A Re-inspection will be performed on or about 10-28-2010.


The tanks on your property must have a permit obtained through the City of Tucson. Below are the codes that require the permit and give the requirements for installation.

3404.2.7.3.2 Vent-line flame arresters and venting devices. Vent-line flame arresters and venting devices shall be installed in accordance with their listings. Use of flame arresters in piping systems shall be in accordance with API 2028.


3404.2.7.3.3 Vent pipe outlets. Vent outlets on atmospheric tanks storing Class IIIB liquids are allowed to discharge inside a building if the vent is a normally closed vent.
" Install the required vents, if the tanks are indoors install the "Normally closed or Pressure/ vacuum" type vent


3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. The venting shall be installed and maintained in accordance with Section 2.2.5.2 of NFPA 30.
" Install the required emergency vents.