Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T10FR02091
Inspection Description - INSP - FULL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/14/2010 | INSP - FULL | Correction Required | 1. _____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. - WEST BAY NEER FLAMMABLE LIQUIED STORAGE AREA 2. _____ 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used: - PLACE A BLANK NI THE ELECTRICLA PANEL WHERE BREAKER IS MISSING 3. _____ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. - FIRE EXTINGUISHERS SHALL BE SERVICED ANNUALLY (LAST 2009) - PROVIDE THE PROPER EXTINGUISHER IN WEST BAY 4. _____ 1504.4 Fire protection. Spray booths and spray rooms shall be protected by an approved automatic fire-extinguishing system complying with Chapter 9 which shall also protect exhaust plenums, exhaust ducts and both sides of dry filters when such filters are used. - Provide automatic sprinkler coverage in accordance with chapter 15 - YOUR BOOTH IS MADE OF COMBUSTINLE MATERIAL. yOU ARE HEREBY ORDER TO CEASE AND DESIST ALL SPRAYING OPERATIONS UNTIL YOU HAVE A PROPER SPRINKLERED BOOTH. |
|
10/14/2010 | INSP - FULL | Correction Required | UPON RE-INSPECTION THE OWNER HAS CHAGED T OWATER BASED PAINTS ALL ITEMS ABATED |
|
10/14/2010 | INSP - FULL | Approved |