Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T10FR02037

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
11/02/2010 VIOL - FIRE PROTECTION SYSTEMS Approved ALL REPAIRED AND UP TO DATE REPORT GIVEN
10/05/2010 VIOL - FIRE PROTECTION SYSTEMS Denied The Tucson Fire Department records indicate that above address has not completed a fire sprinkler inspection since 08/15/2002 Tucson Fire code Section Appendix C states the following:

Appendix C Inspection and testing. Inspection and testing on water-base fire protection systems shall be done annually.
C102.11 Check Valves. Check Valves shall be internally inspected every five years to verify that all components operate properly and are in good condition.

The following pass due report(s) shall be in by 10/28/2010

___XX___Annual fire sprinkler inspection report.

___XX___5 year check valve inspection report.
10/05/2010 VIOL - FIRE PROTECTION SYSTEMS Denied Repair all tamper switches to Building #5