Inspection Status: Denied
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T10FR02033
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/04/2010 | VIOL - FIRE PROTECTION SYSTEMS | Denied | The Tucson Fire Department received a fire sprinkler inspection report showing deficiencies, under the Tucson Fire Code states the following: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. According to the fire sprinkler inspection report that was received from United Fire the following deficiencies shall be repaired: 1. 2 painted heads in the mechanical room (Replace) 2. 1 painted head in room 121 (Replace) 3. 1 empty bulb in room 100 (Replace) An re-inspection of the above conditions will be done on October 28, 2010. |