Case: T10FR02032

Parcel: 13336014E


Addresses:

9595 E BROADWAY BL


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR02032

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
11/02/2010 VIOL - MEANS OF EGRESS Approved All approved / closed.
10/04/2010 VIOL - MEANS OF EGRESS Violation Panic hardware hard to open:

TFC2006 / 1028.8 [Tucson Fire Code Modifications] Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code.


1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following:
1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width.
2. A maximum unlatching force of 15 pounds (67 N).

______ Repair door to comply with 15lb force requirement.