Case: T10FR02032

Parcel: 13336014E


Addresses:

9595 E BROADWAY BL


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T10FR02032

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
11/02/2010 VIOL - FIRE PROTECTION SYSTEMS Approved
10/04/2010 VIOL - FIRE PROTECTION SYSTEMS Violation Grease collector / screens:
904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall
state the extent, time and date of cleaning. Such records shall be maintained on the premises.

______ Keep hood screens clean at all times [maybe clean daily or weekly], also check to see where grease collects and let me know what happens to it. [service deli]
10/04/2010 VIOL - FIRE PROTECTION SYSTEMS Violation Escutcheons:

903.3.1 Standards. Sprinkler systems shall be designed
and installed in accordance with Sections 903.3.1.1,
903.3.1.2 or 903.3.1.3.

______ Repair or replace above item as necessary.