Case: T10FR01959

Parcel: 133231840


Addresses:

991 N PANTANO RD


Inspection Status: Correction Required

Inspection History: INSP - AST/UST

Case Number - T10FR01959

Inspection Description - INSP - AST/UST

Inspection Status - Correction Required

Date Description Inspector Results Comments
09/23/2010 INSP - AST/UST Correction Required 09-22-2010
Brake Max
991 N Pantano
Tucson, AZ 85710

Dear Sir or Madam,

The Tucson Fire Department has conducted a fire safety inspection at the above stated business on 09-21-2010. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code with modifications. A Re-inspection will be performed on or about 10-05-2010.


The tanks on your property must have a permit obtained through the City of Tucson. Below are the codes that require the permit and give the requirements for installation.

3404.2.7.3.3 Vent pipe outlets. Vent outlets on atmospheric tanks storing Class IIIB liquids are allowed to discharge inside a building if the vent is a normally closed vent.
" Install the required vents, if the tanks are indoors install the "Normally closed or Pressure/ vacuum" type vent

3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. The venting shall be installed and maintained in accordance with Section 2.2.5.2 of NFPA 30.
" Install the required emergency vents.




Re-Inspected by __________________ Approved Disapproved

Sincerely,


Conrad Funke
Fire Inspector
Tucson Fire Department
(520) 837-7111