Case: T10FR01956

Parcel: 12106222A


Addresses:

5545 E LEE ST

Inspection Status: Correction Required

Inspection History: INSP - FULL

Date Description Inspector Results Comments
09/22/2010 INSP - FULL Correction Required United Fire Rpt- Non Compliance tag on system.
09/22/2010 INSP - FULL Approved A NEW GRILL AND 6 BURNER RANGE WERE INSTALLED IN 2007. THESE WERE INSTALLED IN THE OPPOSITE POSITION OF THE OLD UNITS CREATING AN IMPROPER COVERAGE ISSUE. THIS WAS NOT NOTED ON SUBSEQUENT INSPECTION REPORTS UNTIL NOW. UNITED FIRE RE-ARRANGED THE HEADS TO PROVIDE CORRECT COVERAGE AND REMOVED THE TOP SHELF FROM THE RANGE. THE KITCHEN NOW HAS PROPER EXTNGUISHMENT COVERAGE. THIS COMPLAINT IS CLOSED.