Case: T10FR01951

Parcel: 13320128A


Addresses:

602 N WILMOT RD


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR01951

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
10/15/2010 VIOL - MEANS OF EGRESS Approved
09/22/2010 VIOL - MEANS OF EGRESS Violation Panic Hardware with keyed dead bold:

TFC2006 / 1028.8 [Tucson Fire Code Modifications] Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code.

______Remove dead bolt lock. [Portico gate]
09/22/2010 VIOL - MEANS OF EGRESS Violation Emergency lighting:

IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located]

______Fix all inoperative emergency lights. [Mulvaney kitchen, Main church]