Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T10FR01951
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/15/2010 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
09/22/2010 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Hood system[s] not tagged / inspected: TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ______ Hood system shall be maintained, inspected and tagged [semi- annually] in accordance with this code. [Kitchen system has no year "punched" on card] ______ The kitchen used for warming water, per the code must be maintained if it is present, regardless of its use. The code states "maintained" or "removed". Thank you. |
|
09/22/2010 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Extinguishers not mounted: TFC2006/ 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm). ______ Mount extinguishers in an approved manner. [Mulvaney kitchen] |