Case: T10FR01951

Parcel: 13320128A


Addresses:

602 N WILMOT RD


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T10FR01951

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
10/15/2010 VIOL - FIRE PROTECTION SYSTEMS Approved
09/22/2010 VIOL - FIRE PROTECTION SYSTEMS Violation Hood system[s] not tagged / inspected:

TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

______ Hood system shall be maintained, inspected and tagged [semi- annually] in accordance with this code. [Kitchen system has no year "punched" on card]

______ The kitchen used for warming water, per the code must be maintained if it is present, regardless of its use. The code states "maintained" or "removed". Thank you.
09/22/2010 VIOL - FIRE PROTECTION SYSTEMS Violation Extinguishers not mounted:

TFC2006/ 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm).

______ Mount extinguishers in an approved manner. [Mulvaney kitchen]