Case: T10FR01951

Parcel: 13320128A


Addresses:

602 N WILMOT RD


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T10FR01951

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
10/15/2010 VIOL - BUILDING SVCS & SYSTEMS Approved
09/22/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Electrical wires extending through ceiling:

TFC2006/ 605.5 Flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors.

______ Please remove wires. [classrooms x 2]
09/22/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords:

TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____ Remove or replace with approved fused power strip.
09/22/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Courtyard lights:
TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.

______These string lights look old and dangerous. Please disable lights so no electricity can pass. They may be left in place. [both patios - Labrynth, and Creswell courtyard with the vines overgrown.]

_____ Remove lights from the Anderson classroom, along with the extension cord.
09/22/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Multiplug adapters:

TFC2006/ 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

______Remove noncomplying devices. [School kitchen]