Case: T10FR01933

Parcel: 11206014A


Addresses:

2736 N CAMPBELL AV


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T10FR01933

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
09/15/2010 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.4.2 Power supply
Relocatable power taps shall be directly connected to a permanently installed receptacle.

____Remove daisy-chained multi-plug adapters.
09/15/2010 VIOL - BUILDING SVCS & SYSTEMS Correction Required 603.1

IFGS 407.2 Design and installation.
Piping shall be supported with pipe hooks, metal pipe straps, bands, brackets, or hangers suitable for the size of piping, of adequate strength and quality, and located at intervals so as to prevent or damp out excessive vibration. Piping shall be anchored to prevent undue strains on connected equipment and shall not be supported by other piping. Pipe hangers and supports shall conform to the requirements
of MSS SP-58 and shall be spaced in accordance with Section 415. Supports, hangers, and anchors shall be installed so as not to interfere with the free expansion and contraction of the piping between anchors. All parts of the supporting equipment
shall be designed and installed so they will not be disengaged by movement of the supported piping.