Case: T10FR01926

Parcel: 13323106A


Addresses:

600 N KOLB RD

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
10/01/2010 VIOL - BUILDING SVCS & SYSTEMS Approved
09/15/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Open space in electrical panel:

TFC2006 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.

_____Place an approved "blank" in the space. [room 5]

_____ Cover wires in the electrical box [with an approved cover] in room 5.
09/15/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Multiplug adapters:

TFC2006/ 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

______Remove noncomplying devices.
09/15/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords (used for permanent wiring]:

TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____ Remove or replace with approved fused power strip. [Heavy duty cords may be used temporarily however.]