Case: T10FR01925

Parcel: 13333033A


Addresses:

9100 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
11/03/2010 VIOL - MEANS OF EGRESS Approved All approved - Good job! / closed.
09/15/2010 VIOL - MEANS OF EGRESS Violation Exit Signs- light and back up power:
1011.5.3 Power source. Exit signs shall be illuminated at
all times. To ensure continued illumination for a duration of
not less than 90 minutes in case of primary power loss, the
sign illumination means shall be connected to an emergency
power system provided from storage batteries, unit equipment
or an on-site generator. The installation of the emergency
power system shall be in accordance with Section
2702 of the International Building Code.

______ Repair all exit signs and battery back up system.
09/15/2010 VIOL - MEANS OF EGRESS Violation Exit access, exit, and discharge path blocked:
1027.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other
emergency. Security devices affecting means of egress shall be subject to approval of the fire code official.

______ Clear exit path and keep it clear [36" minimum]
09/15/2010 VIOL - MEANS OF EGRESS Violation Exit signs:
TFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.

______Place exit signs in an approved manner over the three specified doors in the pre-school building.
09/15/2010 VIOL - MEANS OF EGRESS Violation Emergency lighting:

IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located]

______Fix all inoperative emergency lights.
09/15/2010 VIOL - MEANS OF EGRESS Violation Double keyed lock on door:
1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

______ Remove Keyed dead bolt. [screen door - pre-school]