Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T10FR01924
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Violation
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/15/2010 | VIOL - MEANS OF EGRESS | Violation | TFC 1006 MEANS OF EGRESS ILLUMINATION 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times *Verify that all emergency egress light kits operate properly (including those in stairways) TFC 1011 EXIT SIGNS 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. *Install approved Exit signs at door leading to the east exit from the Public Access Gallery; and one at door in Print/Copy Area leading to the Gallery *Install additional signs as necessary to comply with the above placement requirements. TFC 1027 MEANS OF EGRESS FOR EXISTING BUILDINGS 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. *Repair all exit sign illumination |