Case: T10FR01924

Parcel: 117170030


Addresses:

124 E BROADWAY BL


Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T10FR01924

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
03/15/2010 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 903
AUTOMATIC SPRINKLER SYSTEMS
901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.
*Verify (by a Qualified Person) adequate sprinkler coverage in Reception Lobby.
*Remove all wires and cables attached to, or hanging on any portion of the fire
sprinkler system (including sprinkler piping and its hangers).
*Provide the most recent Fire Sprinkler Test Report to TFD.
*Provide unobstructed access to all fire protection equipment (ie. risers and valves).
*Install sprinkler guards at all heads in hazardous locations and those< 8' above floor.