Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T10FR01924

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
03/15/2010 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605
ELECTRICAL EQUIPMENT, WIRING AND HAZARDS
605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. ... Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical
shock or fire hazard shall not be used.
*Abate open wiring in basement Mech. Room -- *Abated 3/15
*Abate non protected exterior outlet and install dead front at yard electrical panel
*Abated 3/15
*Install GFI outlets, per NEC, at wet locations.
*Remove and/or replace all non-listed fixtures, switches etc.
*Install electric pane cover doors (2) in Studio B.
*Provide guards at all exposed bulbs < 8' above floor and any other location
where bulb breakage is likely.
*Verify safety (height) of feed line entering southeast corner of building .
03/15/2010 VIOL - BUILDING SVCS & SYSTEMS Violation 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated working space.
*Provide clear access to all electrical panels
03/15/2010 VIOL - BUILDING SVCS & SYSTEMS Violation 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible
and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting
means for each service, feeder or branch circuit originating on a switchboard or panel board shall
legibly and durably marked to indicate its purpose unless such purpose is clearly evident
*All electrical panels shall be labeled and panel schedules provided.
*Install signage to all doors leading to electrical panels
03/15/2010 VIOL - BUILDING SVCS & SYSTEMS Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with
portable appliances.
*Remove all extension cords used as permanent wiring and/or
extended through walls or floors.