Case: T10FR01924

Parcel: 117170030


Addresses:

124 E BROADWAY BL


Inspection Status: Violation

Inspection History: VIOL - FIRE SERVICE FEATURES

Case Number - T10FR01924

Inspection Description - VIOL - FIRE SERVICE FEATURES

Inspection Status - Violation

Date Description Inspector Results Comments
03/15/2010 VIOL - FIRE SERVICE FEATURES Violation TFC 506
KEY BOXES
506.1 Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall
be of an approved type and shall contain keys to gain necessary access as required by the fire code official.
*Provide an approved Key Box at main entry with keys to all
doors leading to fire equipment or electrical panels and shut-offs.
03/15/2010 VIOL - FIRE SERVICE FEATURES Violation TFC 510
FIRE DEPARTMENT ACCESS TO EQUIPMENT
510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for …, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
*Install signage to all doors leading to fire equipment (ie. Sprinkler valves)