Case: T10FR01924

Parcel: 117170030


Addresses:

124 E BROADWAY BL


Inspection Status: Violation

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Case Number - T10FR01924

Inspection Description - VIOL - PRECAUTION AGAINST FIRE

Inspection Status - Violation

Date Description Inspector Results Comments
03/15/2010 VIOL - PRECAUTION AGAINST FIRE Violation TFC 304
COMBUSTIBLE WASTE MATERIAL
304.3.3 Capacity exceeding 1.5 cubic yards. Dumpsters shall not be placeded within 5 feet of combustible walls, openings or combustible roof eave lines.
*Dumpster on East side shall be relocated 5' from building openings
(including windows).
03/15/2010 VIOL - PRECAUTION AGAINST FIRE Violation TFC 313
FUELED EQUIPMENT
313.1 General. Fueled equipment, including but not limited to motorcycles, mopeds, lawn-care equipment and portable cooking equipment, shall not be stored, operated or repaired within a building.
*Remove generator from Public Check-out & Storage Area
03/15/2010 VIOL - PRECAUTION AGAINST FIRE Violation TFC 315
MISCELLANEOUS COMBUSTIBLE MATERIALS STORAGE
315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms.
*All combustible material shall be removed from all equipment rooms
and any non-sprinklered plenum spaces.